ECOAZUR® System at NBA Headquarters

At a Glance
NBA Headquarters
  • Case Study
  • Office & Commercial
  • July 2020
The Objective
The NBA Headquarters in New York City worked with Kitchen Energy Solutions on their goal to increase energy savings at the cafeteria. The challenge presented for this kitchen was due to their multiple hoods being connected to a single exhaust fan.

In new construction projects in New York City, there are typically space restrictions when it comes to the HVAC system in commercial kitchens. For this reason, many kitchens are designed with one kitchen exhaust fan to serve multiple kitchen hoods. A DCKV system can be difficult to select with this type of design, and a modulating damper system is a must to save energy.

Our team was left to determine how energy savings could be achieved with this multiple hood-single fan layout.

Estimated Preliminary Analysis

Average New Fan Speed65%
Electrical Savings (Kilowatt-Hour/Year)60,862 kWhper Year
Electrical Savings ($/Year)$9,125.00per Year
Heating Savings ($/Year)$3,649.00per Year
Cooling Savings ($/Year)$235.00per Year
Payback Timeline1.8 years ROI

Values below are based on 11 hours of Runtime per Day with a Total Controlled CFM of 10,300 and Total Controlled HP of 30.

The Solution
ECOAZUR® was the perfect solution for the cafeteria at NBA Headquarters, offering the ability to retrofit modulating dampers on all hoods in combination with the ECOAZUR® optic and temperature sensors, ultimately maximizing the energy savings in their kitchen.

The ECOAZUR® system was the perfect DCKV solution for this commercial kitchen’s design. Since ECOAZUR®’s dampers require no cutting or welding, this allows the system to be installed into any commercial kitchen hood or ductwork. On this particular job site, the duct work design had to change along the way, and ECOAZUR® was able to adapt and utilize its dampers as a balancing solution prior to being set for its energy saving settings.

As a more cost-effective option compared to other systems on the market, the ECOAZUR® system is a slam dunk.

The Results

Post Installation Analysis

(Actual Results)(Difference from Estimated Analysis)
Average New Fan Speed50%- 15%
Electrical Savings (Kilowatt-Hour/Year)71,611 kWh+ 10,749per Year
Electrical Savings ($/Year)$10,742.00+ $1,617.00per Year
Heating Savings ($/Year)$4,293.00+ $644.00per Year
Cooling Savings ($/Year)$296.00+ $61.00per Year
Payback Timeline1.6 years- 0.2 yearsROI

Values below are based on 11 hours of Runtime per Day with a Total Controlled CFM of 10,300 and Total Controlled HP of 30.

Simple Payback
0 yrs
The NBA Headquarters’ DCKV investment was repaid within 1.6 years
Total Dollars Saved per Year
$0
Combined electrical, heating + cooling savings of $15,331 per year
Average New Fan Speed
0%
Average fan speed decreased from 100% to 50% with ECOAZUR®
CO2 Reduction per Year
0k
Yearly carbon dioxide reduction of 634,030 lbs